Screened one-gang junction box

Screened one-gang box / one-gang junction box

Screened one-gang box / one-gang junction box
Preview: Screened one-gang box / one-gang junction box
Screened one-gang box / one-gang junction box
  • 9064-88
  • 4013456220805
  • with screening and potential downlead
For panel thickness
7 - 40 mm
Depth
68 mm
Cut hole Ø
68 mm
Screw spacing
60 mm
Device screws
2
Break-out openings Ø 20 mm
4
Cable entries 3 x 2.5 mm² or 5 x 1.5 mm²
2
Cable entries 3 x 1.5 mm²
4
Cable entries for low voltages
2
Packaging inner/dispatch
10/100
Product information

Screened one-gang junction box

Screened one-gang junction box for cavity wall installation. The conductive coating suppresses interference with a high alternating field component, whether radiated or received.

  • For environmentally-safe electrical installation, biological construction
  • With screening and potential conductivity
  • The functional earth of the box must only be connected to the potential equalisation and not to the equipment grounding conductor (PE conductor)

Installation

Remove cable sheath and screen with AMZ 2 (Art. No. 1190-02). Fit bare tracer wire with transparent insulating hose.

Connect functional earth of the box to tracer wires of screened cable.

As a junction box, connect the box cover's functional earth to the tracer wires of the cables.

Attach cover to box with device screws.

Technical processing instructions/standards

  • dimensions in accordance with German DIN 49073
  • for rooms used for medical purposes, environmentally-friendly construction, etc.
  • the conductive coating suppresses interference with a high alternating field component, whether radiated or received
  • The functional earth of the box must only be connected to the potential equalisation and not to the equipment grounding conductor (PE conductor)
  • Not suitable for use in X-ray or radiation rooms!