Safety for X-ray rooms. One-gang junction box for radiation protection walls.

Support connector

Support connector
Preview: Support connector
Support connector
  • 9060-74
  • 4013456537408
  • For fully insulated through-wiring in combinations
  • for Art. No. 9074-01
Packaging inner/dispatch
25/100
Product information

Safety for X-ray rooms. One-gang junction box for radiation protection walls.

KAISER's innovative radiation protection box protects against radiation used for medical purposes, e.g. in X-ray facilities. The high density of the radiation protection compound absorbs soft and hard X-rays. The box is especially suitable for lead-free radiation protection walls (e.g. Knauf Safeboard) and - because of its dose-reducing effect in the tube voltage range between 40 - 150 kV - guarantees a lead-equivalent value for the wall of up to 3 mm Pb even with opposing installation. In addition, the box can easily be used in lead-lined walls. In this case, the radiation protection box achieves a lead-equivalent value of 1.5 mm Pb with walls which are leadlined on one side.

  • Protection against X-rays
  • Suitable for lead-free radiation protection walls
  • Lead-free - no health risks
  • Retrofitting is possible
  • Fast installation without additional screening measures
  • Opposing installation is possible
  • Maintains the wall's sound insulation protection

Examples of use

Example of installation of a switch/socket combination.

Installation of the radiation protection box in the wall.

Opposing use of the radiation protection box.

Use of the radiation protection box in a triple combination.

Allocation table for universal opening cutters

Installation

Use a cutter (e.g. PROFI: Art. No. 1081-20) to make a Ø 74 mm opening.

Installation then proceeds as with a conventional cavity wall box.

Secure and fast installation thanks to KAISER FX⁴ technology.

Accurate entries ensured by using the universal opening cutter (Art. No. 1085-80).

For combinations, cut off the marked edge strip.

Combinations at a standard spacing of 71 mm.

The fully-insulated through-wiring is carried out with the support connector.

Depending on the wall construction, the radiation protection box protects the wall up to a lead equivalent of 3 mm Pb.

Certificates
Certificate

Technical Report Testing the radiation protection properties (Art.-Nr. 9074-01)

2.9 MB

Select download
Download
Product data sheet

Support connector

Article no: 9060-74

Download
Brochure

Radiation protection

Electrical installation in radiation protection walls.

1.9 MB | 2018-01-31

Flyer

Herzstück jeder Installation. - Die KAISER-Dose.

Instruction

Radiation-protection one-gang junction box

for lead-free radiation protection walls, Assembly instructions, Art. No. 9074-01