Cable sealing system LS 90, conduit sealing system RS 90

Cable sealing system LS 90

Cable sealing system LS 90
Preview: Cable sealing system LS 90
Cable sealing system LS 90
  • 9459-01
  • 4013456536234
  • for EI90 fire-protection walls
  • for wall entry, wall outlet and penetration
  • without use of fire-protection foam or putty
  • made of intumescent material
  • automatic room separation of the installation opening
  • unlimited building material shelf life
Min. wall thickness
100 mm
Installation opening (cavity wall)
20 mm
Installation opening (masonry)
20 mm
for cables
5 - 15 mm
ETA approval
ETA-17-0449
for sound insulation walls up to
76 dB
Packaging inner/dispatch
10/100
Product information

Cable sealing system LS 90, conduit sealing system RS 90

Pipe and fire-retardant systems for safe closure of passages and entrances in fire-protection walls. The certified retardants are quick and easy to install and can even be superimposed on cables and pipes retrospectively (EI90). In addition, the cable sealing system can also be used as a wall outlet that enables the connection of electrical attachments.

  • Secure, visible, certified fire sealings
  • For wall feed-throughs and entries
  • Without filling and smoothing
  • Automatic sealing of the joints
  • For cables from Ø 5 - 15 mm
  • For conduits M16 - M25

Examples of applications for cable sealing system LS 90

Wall feed-through in plasterboard fire-protection wall.

Suitable for wall entry and wall outlet in dry construction fire protection wall.

Wall feed-through in a sand-lime brick fire-protection wall.

Wall feed-through in concrete fire-protection wall.

Secure wall outlet up to EI90 for connecting electrical attachments...

...like motion detectors.

Secure wall outlet up to EI90 for connecting electrical attachments...

...like wall lights.

Installation of cable sealing system LS 90 in cavity walls

Cut an installation opening Ø 20 mm using a cutter (e.g. KAISER hardened metal cutter Art. No. 1088-06) or drill.

To install, open the sealing sideways and slide it over the cable.

Press both sides of the sealing into each opening.

The cable sealings can be arranged vertically or horizontally to form a group with a centre distance of 50 mm.

Populating the sealing system

The cable sealing system LS 90 is suitable for all cable cross-sections from 5 – 15 mm (up to 5 x 2.5²).

The conduit sealing system RS 90 can accommodate the following conduit sizes: M16, M20 and M25.

The conduit sealing system RS 90 can also be used as a reserve seal. For this purpose, the conduits must be sealed with KAISER sealing plugs.

Conduit sealing system RS 90 with M16, M20 and M25 conduits.

Technical information

Cable and conduit sealing systems provide tested safety for cavity wall, masonry or concrete constructions.

The installation openings can be made in solid walls using conventional drills (20 mm or 32 mm) or in plasterboard walls using a cutter Ø 35 mm (Art. No. 1084-35).

The cable and conduit sealing systems are manufactured from a permanently durable and flexible material.

By opening the cable and conduit sealing, it can easily be placed around the cable or conduit.

KAISER seals ensure room separation without the need for additional filler.

Mounting cable sealing system LS 90 in solid walls

Make an installation opening using a Ø 20 mm drill.

Open the side of the cable sealing system LS 90, slide it over the cable and press into the opening.

Attach the identification tag.

Officially required identification of the cable sealing.

Certificates
Certificate

Classification report according to EN 13501-2:20216 for products in cross laminated timber walls

Certificate

LS 90 / RS 90 - Type approval (Z-19.53-2531)

Certificate

LS 90: 9459-01_RS 90: 9459-02 - Schallschutzgutachten

Certificate

Cable sealing system LS 90, conduit sealing system RS 90 - European Technical Assessment ETA

588.6 KB

Select download
Certificate

Test report for FlamoX®, LS 90 and RS 90, fire load from below

Download
Product data sheet

Cable sealing system LS 90

Article no: 9459-01

Download
Brochure

Fire protection.

Box, housing and sealing systems for fire-protection walls and ceilings.

6.6 MB | 2024-02-28

Instruction

Cable Sealing System LS 90 / Conduit Sealing System RS 90

Assembly instructions, Art. No. 9459-01, 9459-02

2.4 MB | 2021-03-04

Performance declaration

Declaration of performance

Cable sealing system LS 90, Art. No. 9459-01

1.8 MB | 2020-11-02

Select download
Performance declaration

KAISER Template Confirmation

Submission certificate from the specialist craft company for the client

32.2 KB | 2018-06-26