Ceiling penetration sealing systems DS 90 / 120 mm and DS 90 / 74 mm

Ceiling penetration sealing system DS 90 / 74 mm

Ceiling penetration sealing system DS 90 / 74 mm
Preview: Ceiling penetration sealing system DS 90 / 74 mm
Ceiling penetration sealing system DS 90 / 74 mm
  • 9459-05
  • 4013456544697
  • for fire protection ceilings EI30 - EI90
  • Easy installation without filling
  • Installation on the upper side of the ceiling
  • creates a smoke-tight room separation
Installation opening Ø
100 mm
Ceiling thickness
150 - 300 mm
Cable entries
Maximum population (internal diameter 40 mm)
DIBt approval
Z-19.53-2189
PVC conduits up to
M40
Packaging inner/dispatch
1/12
Product information

Ceiling penetration sealing systems DS 90 / 120 mm and DS 90 / 74 mm

KAISER ceiling penetration sealing systems DS 90 / 120 mm and DS 90 / 74 mm ensure that the ceiling maintains fire-resistance class EI30 - EI90. To efficiently prevent the spread of fire and flue gases through cable penetrations and electrical installation conduits through concrete or cellular concrete ceilings, their fire sealing must have the same fire-resistance class as the ceiling. The ceiling penetration sealing system DS 90 accomplishes this easily, quickly and reliably.

  • Secure, visible, certified fire sealings
  • Sealing especially for ceiling penetrations
  • Automatic sealing without filling or smearing
  • Non-destructive retrofitting
  • Also for mixed population of bundles of cables and conduits
  • Easy and quick installation from above

Examples of use

Use in EI30–EI90 concrete ceilings.

Use in EI30–EI90 cellular concrete ceilings.

Mixed population of cables and conduits up to maximum population. They can also be arranged as groups with a distance of 205 mm (DS 90 / 120 mm) or 125 mm (DS 90 / 74 mm).

Mixed population of cables and conduits up to maximum population.

Population of ceiling penetration sealing system DS 90 / 120 mm and DS 90 / 74 mm

Mixed population of sheathed cables and conduits.

Can also be used as a reserve sealing.

Maximum population with sheathed cables Ø 29 mm and conduits up to M63.

Maximum population with sheathed cables Ø 15 mm and conduits up to M40.

Technical information on ceiling sealing system DS 90 / 120 mm and DS 90 / 74 mm

Divisible installation sleeve with edge protection made of intumescent material.

Retaining springs for quick and secure installation from above.

Cut-outs for receiving the metal plates and for fastening the box sealing system

Divisible installation sleeve for retrofitting of existing cables and conduits.

Making for the location of the screws.

Sealing flange ensures a clean and smoke-tight room separation of the component opening.

For core drill holes Ø 150 mm (DS 90 / 120 mm) and Ø 100 mm (DS 90 / 74 mm).

Two ceiling penetration sealing systems for different applications.

Installation

Installation is identical for ceiling penetration sealing systems DS 90 / 120 and DS 90 / 74 mm, except for the differences in the dimensions.

Making a core drill hole 150 mm or 100 mm.

Insert the installation sleeve from the upper side of the ceiling

Feed sheathed cables and/or conduits through the installation sleeve.

Place sealing cylinder around the cables or conduits and insert into the installation sleeve.

Align plate screws of the sealing cylinder with the markings and tighten.

Place sealing cylinder around the cables or conduits and then snap into place with the sealing cylinder.

The ceiling penetration sealing systems can also be arranged as a group with a distance of 205 mm or 125 mm.

Ceiling penetration sealing systems in concrete or cellular concrete ceilings of 150 – 300 mm ceiling thickness have been approved for use.

Formwork body

For preparation of installation in concrete ceilings, KAISER provides a formwork unit for matching cut-outs.

Adapt formwork unit to the ceiling thickness by cutting it to length.

Fix formwork unit with tie wire to the reinforcement.

After formwork removal, remove the formwork unit from the component opening without leaving any residues.

Non-destructive retrofitting of single cables and conduits

Loosen the sealing element by turning it a quarter of a turn and open it.

Open the sealing element and remove it.

Insert the new cables and conduits.

Turn sealing element around, lock and fix by applying a quarter turn to the right.

Table of max. external diameter of sheathed cables (NYM cables)

The table shows examples of cables which can be used on the basis of the maximum permitted diameter. The main factor is the minimum stated standard diameter acc. to DIN VDE 0250-204.

Certificates
Certificate

Wall- and Ceiling penetration sealing system DS 90 - 74 mm - General building approval (Z-19.53-2189)

Certificate

VKF approval 25349 Fire-sealing system for ceilings DS 90 / 74 mm

238.6 KB

Certificate

Wall- and Ceiling penetration sealing system - European Technical Assessment ETA

4.8 MB

Select download
Download
Product data sheet

Ceiling penetration sealing system DS 90 / 74 mm

Article no: 9459-05

Download
Brochure

Fire protection.

Box, housing and sealing systems for fire-protection walls and ceilings.

6.6 MB | 2024-02-28

Instruction

Fire sealings DS 90

Assembly instructions

2.3 MB | 2023-03-21

Performance declaration

KAISER Template Confirmation

Submission certificate from the specialist craft company for the client

32.2 KB | 2018-06-26

Performance declaration

Declaration of performance

Ceiling penetration sealing system DS 90 / 74 mm, Art. No. 9459-05